Wire Size Calculator — AWG (NEC) & mm² (IEC)

Find the copper wire size for a circuit from load, voltage and run length: NEC Table 310.16 ampacity with temperature and conductor-count derating, breaker sizing and voltage drop in AWG — or IEC/KEC sizing in mm².

STEP 1

Circuit and load

STEP 2

Conductor and conditions

Copper THHN/THWN-2 in raceway. Derating starts from the 90 °C column, but the result cannot exceed the termination column.

Termination rating (NEC 110.14(C))

Most breakers and equipment are listed for 75 °C. For circuits of 100 A or less with unmarked terminals, use 60 °C.

Attics and rooftops run hotter — size for the worst case. ×1.00

This circuit alone is 2. Four or more triggers NEC 310.15(C)(1) adjustment (×1.00 now). Neutrals of balanced circuits and grounds don't count.

STEP 3

Voltage drop limit

NEC 210.19(A) Informational Note: 3% for a branch circuit and 5% total including the feeder are recommended (not mandatory, but widely specified).

Copper ampacity chart (NEC Table 310.16, 86 °F, ≤ 3 conductors)

Size60°C TW, UF, NM-B*75°C THW, THWN90°C THHN, THWN-2mm²
14 AWG1520252.08
12 AWG2025303.31
10 AWG3035405.26
8 AWG4050558.37
6 AWG55657513.30
4 AWG70859521.15
3 AWG8510011526.66
2 AWG9511513033.63
1 AWG11013014542.41
1/0 AWG12515017053.51
2/0 AWG14517519567.44
3/0 AWG16520022585.03
4/0 AWG195230260107.22
250 kcmil215255290126.68
300 kcmil240285320152.01
350 kcmil260310350177.35
400 kcmil280335380202.68
500 kcmil320380430253.35
600 kcmil350420475304.02

* NM-B uses the 60 °C column. 14, 12 and 10 AWG copper are limited to 15, 20 and 30 A breakers by NEC 240.4(D), whatever the table says.

Share this tool

Related Tools

🪜Cable Tray Bend & Offset Calculator
⚡KEC Grounding Calculator
🔧Pipe Size, Slope & Flow Calculator
🔌Resistor Color Code Calculator
📝Character Counter
📐Pyeong to m² Converter

How this wire size calculator picks a wire gauge

In US NEC mode, the calculator starts from the load current — multiplied by 125% for continuous loads that run three hours or more (NEC 210.19 and 210.20) — and picks the next standard breaker from NEC 240.6(A). It then finds the smallest copper conductor whose ampacity covers that breaker: the NEC Table 310.16 90 °C value for THHN/THWN-2 is corrected for ambient temperature (310.15(B)(1)) and for more than three current-carrying conductors in a raceway (310.15(C)(1)), and the result is capped at the 60 °C or 75 °C column of the terminals (110.14(C)), or at the 60 °C column for NM-B cable (334.80). The small-conductor rule (240.4(D)) still limits 14, 12 and 10 AWG to 15, 20 and 30 A breakers. Finally the voltage drop is checked with VD = 2·K·I·L/CM for single-phase or 1.732·K·I·L/CM for three-phase, K = 12.9, against the 3% branch-circuit recommendation. For example, a 20 A, 120 V circuit 100 feet long passes on ampacity with 12 AWG, but 12 AWG drops 6.6%, so 8 AWG is needed to stay under 3%. In IEC/KEC mode the same logic uses mm² conductors: A conductor must pass three checks. First, pick a breaker at or above the load current, and the cable ampacity must be at least the breaker rating (KEC 212.4.1, IB ≤ In ≤ IZ). Ampacity comes from the IEC 60364-5-52 Annex B tables that the Korean Electrical Code adopts, by insulation (PVC 70 °C, XLPE 90 °C) and installation method (A1 conduit in insulated wall, B1 wires in conduit, B2 cable in conduit, C clipped direct, E perforated tray), then corrected for ambient temperature and the number of circuits sharing the route. Second, the voltage drop from the origin to the equipment must stay within KEC 232.3.9 (LV supply: lighting 3 %, other 5 %; HV supply: 6 % and 8 %). Third, indoor LV wiring must be at least 2.5 mm². The calculator recommends the largest size required by the three checks and shows which one governed. For example, a 25 A single-phase 220 V air-conditioner circuit in HFIX wire in conduit (B1), 15 m long, is fine at 2.5 mm² alone at 30 °C, but with three circuits in the conduit at 35 °C it needs 6 mm² to carry the ampacity required by a 30 A breaker.

Common Use Cases

🔌
Long Branch Circuits
A 20 A, 120 V receptacle circuit to a detached garage 100 ft away needs 8 AWG to keep voltage drop under 3%, even though 12 AWG carries the current. The calculator shows which check governs.
❄️
Conduits With Many Circuits
Nine current-carrying conductors in one conduit at 104 °F cut 12 AWG THHN to about 19 A, below a 20 A breaker, so 10 AWG is required — easy to miss without the adjustment table.
📏
Long Runs and Voltage Drop
On runs over 100 m, voltage drop often decides the size. The calculator applies the KEC allowance of 0.005 % per metre beyond 100 m, up to 0.5 %.
🔍
Auditing Existing Circuits
Use the IB ≤ In ≤ IZ chain to spot circuits where the installed breaker is larger than the cable ampacity, so the cable would overheat before the breaker trips.

How to Use

  1. 1
    Enter Supply and Load
    Choose the system (single or three phase), enter load current or kW with power factor, and the one-way cable length from the panel to the load. The example button loads an A/C circuit.
  2. 2
    Choose Wire and Method
    Pick HFIX wire, CV/F-CV cable or PVC types, then the installation method from the pictures. Enter ambient temperature and how many circuits share the conduit or tray.
  3. 3
    Set the Drop Limit
    Select LV or HV supply and lighting or other loads to fill in the KEC limit. If the feeder uses part of the budget, enter only this circuit's share.
  4. 4
    Read the Result
    See the recommended size and what governed it, the load ≤ breaker ≤ ampacity chain, a bar comparison of each check and the actual voltage drop, then copy the result.

Frequently Asked Questions