Find the copper wire size for a circuit from load, voltage and run length: NEC Table 310.16 ampacity with temperature and conductor-count derating, breaker sizing and voltage drop in AWG — or IEC/KEC sizing in mm².
Copper THHN/THWN-2 in raceway. Derating starts from the 90 °C column, but the result cannot exceed the termination column.
Most breakers and equipment are listed for 75 °C. For circuits of 100 A or less with unmarked terminals, use 60 °C.
Attics and rooftops run hotter — size for the worst case. ×1.00
This circuit alone is 2. Four or more triggers NEC 310.15(C)(1) adjustment (×1.00 now). Neutrals of balanced circuits and grounds don't count.
NEC 210.19(A) Informational Note: 3% for a branch circuit and 5% total including the feeder are recommended (not mandatory, but widely specified).
| Size | 60°C TW, UF, NM-B* | 75°C THW, THWN | 90°C THHN, THWN-2 | mm² |
|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | 2.08 |
| 12 AWG | 20 | 25 | 30 | 3.31 |
| 10 AWG | 30 | 35 | 40 | 5.26 |
| 8 AWG | 40 | 50 | 55 | 8.37 |
| 6 AWG | 55 | 65 | 75 | 13.30 |
| 4 AWG | 70 | 85 | 95 | 21.15 |
| 3 AWG | 85 | 100 | 115 | 26.66 |
| 2 AWG | 95 | 115 | 130 | 33.63 |
| 1 AWG | 110 | 130 | 145 | 42.41 |
| 1/0 AWG | 125 | 150 | 170 | 53.51 |
| 2/0 AWG | 145 | 175 | 195 | 67.44 |
| 3/0 AWG | 165 | 200 | 225 | 85.03 |
| 4/0 AWG | 195 | 230 | 260 | 107.22 |
| 250 kcmil | 215 | 255 | 290 | 126.68 |
| 300 kcmil | 240 | 285 | 320 | 152.01 |
| 350 kcmil | 260 | 310 | 350 | 177.35 |
| 400 kcmil | 280 | 335 | 380 | 202.68 |
| 500 kcmil | 320 | 380 | 430 | 253.35 |
| 600 kcmil | 350 | 420 | 475 | 304.02 |
* NM-B uses the 60 °C column. 14, 12 and 10 AWG copper are limited to 15, 20 and 30 A breakers by NEC 240.4(D), whatever the table says.
Share this tool
Related Tools
In US NEC mode, the calculator starts from the load current — multiplied by 125% for continuous loads that run three hours or more (NEC 210.19 and 210.20) — and picks the next standard breaker from NEC 240.6(A). It then finds the smallest copper conductor whose ampacity covers that breaker: the NEC Table 310.16 90 °C value for THHN/THWN-2 is corrected for ambient temperature (310.15(B)(1)) and for more than three current-carrying conductors in a raceway (310.15(C)(1)), and the result is capped at the 60 °C or 75 °C column of the terminals (110.14(C)), or at the 60 °C column for NM-B cable (334.80). The small-conductor rule (240.4(D)) still limits 14, 12 and 10 AWG to 15, 20 and 30 A breakers. Finally the voltage drop is checked with VD = 2·K·I·L/CM for single-phase or 1.732·K·I·L/CM for three-phase, K = 12.9, against the 3% branch-circuit recommendation. For example, a 20 A, 120 V circuit 100 feet long passes on ampacity with 12 AWG, but 12 AWG drops 6.6%, so 8 AWG is needed to stay under 3%. In IEC/KEC mode the same logic uses mm² conductors: A conductor must pass three checks. First, pick a breaker at or above the load current, and the cable ampacity must be at least the breaker rating (KEC 212.4.1, IB ≤ In ≤ IZ). Ampacity comes from the IEC 60364-5-52 Annex B tables that the Korean Electrical Code adopts, by insulation (PVC 70 °C, XLPE 90 °C) and installation method (A1 conduit in insulated wall, B1 wires in conduit, B2 cable in conduit, C clipped direct, E perforated tray), then corrected for ambient temperature and the number of circuits sharing the route. Second, the voltage drop from the origin to the equipment must stay within KEC 232.3.9 (LV supply: lighting 3 %, other 5 %; HV supply: 6 % and 8 %). Third, indoor LV wiring must be at least 2.5 mm². The calculator recommends the largest size required by the three checks and shows which one governed. For example, a 25 A single-phase 220 V air-conditioner circuit in HFIX wire in conduit (B1), 15 m long, is fine at 2.5 mm² alone at 30 °C, but with three circuits in the conduit at 35 °C it needs 6 mm² to carry the ampacity required by a 30 A breaker.